xnx Honeywell Analytics xnx xnx Transmitter Manual

Dear readers, here we are offering xnx Honeywell Analytics xnx xnx Transmitter Manual PDF to all of you. You should read and understand this manual before installing, operating, or maintaining the XNX Transmitter. Pay particular attention to the warnings and cautions below. All of the warnings and cautions were shown here are repeated in the appropriate sections of the manual.

Identify hazardous or unsafe practices which could result in severe injury or death.XNX supports Electrochemical, Infrared, and Catalytic Bead gas monitors and uses standard 4-20mA wiring and HART: options include Modbus, Fieldbus (pending) up to three relays, and a local Hart Adapter for configuration and diagnostics using existing HART handheld devices.

xnx Honeywell Analytics xnx xnx Transmitter Manual PDF

Features & Benefits:

  • Flammable gas detection 0 to 100% LFL/LEL
  • Flexible operation options
  • Minimal training required

Quick Specs:

  • Material: LM25 aluminum, painted (SS316 painted optional)
  • Temperature: -40° to +65°C / -40° to +150°F (sensor dependent)
  • Humidity: 20 to 90% RH (non-condensing)

Fire and Gas Consultancy Services

Warning and Instructions

  • Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned.
  • Access to the interior of the sensor, when carrying out any work, must only be conducted by trained personnel.
  • Before carrying out any work ensure local regulations and site procedures are followed. Appropriate standards must be followed to maintain the overall certification of the sensor.
  • To reduce the risk of ignition of hazardous atmospheres, conduit runs must have a seal fitting connected within 18 inches (45 cm) of the enclosure.
  • To reduce the risk of ignition of a hazardous atmosphere, disconnect the equipment from the supply circuit before opening the sensor enclosure. Keep assembly tightly closed during operation.
  • Never open the XNX enclosure under power unless the area is known to be non-hazardous.
  • The sensor must be earthed/grounded for Intrinsic Safety, and electrical safety and to limit the effects of radio frequency interference. Earth/ ground points are provided inside and outside the unit. EMI note for applications using shielded cable: Cable shield terminations must be made at the cable glands with suitable EMI-type glands.
  • Avoid terminating cable shields at the Earth ground lug inside the XNX enclosure. In cases where wiring is in the pipe, a shielded cable is not required. The external terminal is only a supplemental bonding connection where local authorities permit or require such a connection.
  • Take care when handling EC sensor cells as they may contain corrosive solutions.
  • Do not tamper or in any way disassemble the sensor cells.
  • Do not expose to temperatures outside the recommended range.
  • Do not expose the sensor to organic solvents or flammable liquids.
  • At the end of their working lives, sensors must be disposed of in an environmentally safe manner, in accordance with local waste management requirements and environmental legislation. Do NOT incinerate sensors as they may emit toxic fumes.
  • High off-scale readings may indicate an explosive concentration of gas.
  • Verify all outputs, including display, after installation, after service events, and periodically to ensure the safety and integrity of the system.
  • Do not use the XNX Universal Transmitter in oxygen-enriched atmospheres. Concentrations displayed will be adversely affected by oxygen depletion.
  • After changing parameters with a handheld device, verify that the parameter settings are correct at the transmitter.
  • The factory-set passcodes must be reset to prevent unauthorized access to the transmitter’s menus.

You can download xnx Honeywell Analytics xnx xnx Transmitter Manual PDF by clicking on the following download button.


xnx Honeywell Analytics xnx xnx Transmitter Manual PDF Download Link

Report This
If the download link of Gujarat Manav Garima Yojana List 2022 PDF is not working or you feel any other problem with it, please Leave a Comment / Feedback. If xnx Honeywell Analytics xnx xnx Transmitter Manual is a illigal, abusive or copyright material Report a Violation. We will not be providing its PDF or any source for downloading at any cost.